Acts Online
GT Shield

Merchant Shipping Act, 1951 (Act No. 57 of 1951)

Schedules

Second Schedule

Protocol of 1978 Relating to the International Convention for the Safety of Life at Sea, 1974

Annex

Chapter II-2 : Construction—Fire Protection, Fire Detection and Fire Extinction

Part B — Fire Safety Measures for Passenger Ships Carrying More than 36 Passengers

Regulation 19 : Bulkheads within a main vertical zone

 

(a) All bulkheads which are not required to be “A” Class divisions shall be at least “B” Class or “C” Class divisions as prescribed in the tables in Regulation 20 of this Chapter. All such divisions may be faced with combustible materials in accordance with the provisions of Regulation 27 of this Chapter.

 

(b) All corridor bulkheads where not required to be “A” Class shall be “B” Class divisions which shall extend from deck to deck except—
(i) when continuous “B” Class ceilings and/or linings are fitted on both sides of the bulkhead, the portion of the bulkhead behind the continuous ceiling or lining shall be of material which in thickness and composition is acceptable in the construction of “B” Class divisions but which shall be required to meet “B” Class integrity standards only in so far as is reasonable and practicable in the opinion of the Administration;
(ii) in the case of a ship protected by an automatic sprinkler system complying with the provisions of Regulation 12 of this Chapter, the corridor bulkheads of “B” Class materials may terminate at a ceiling in the corridor provided such a ceiling is of material which in thickness and composition is acceptable in the construction of “B” Class divisions. Notwithstanding the requirements of Regulation 20 of this Chapter, such bulkheads and ceilings shall be required to meet “B” Class integrity standards only in so far as is reasonable and practicable in the opinion of the Administration. All doors and frames in such bulkheads shall be of incombustible materials and shall be constructed and erected so as to provide substantial fire resistance to the satisfaction of the Administration.

 

(c) All bulkheads required to be “B” Class divisions, except corridor bulkheads, shall extend from deck to deck and to the shell or other boundaries unless continuous “B” Class ceilings and/or linings are fitted on both sides of the bulkhead in which case the bulkhead may terminate at the continuous ceiling or lining.

 

 


500 - Internal Server Error
500 - Internal Server Error

We're sorry, but something went wrong displaying that page. While we work on fixing this, you can return to the home page.

Alternatively, email [email protected] for assistance.